| Input |
Nominal Voltage
3 phase, 3 wire + ground |
380 VAC (operating range 342 - 418 VAC)
415 VAC (operating range 373 - 456 VAC)
440 VAC (operating range 396 - 484 VAC)
480 VAC (operating range 432 - 528 VAC) |
| Frequency |
50 Hz through 60 Hz |
| Power Factor |
Greater than 92% at maximum power |
| |
| Environmental |
| Operating Temperature |
0°C to 50°C |
| Storage Temperature |
-25°C to +85°C |
| Air Cooling |
Front and rear air intake, top exhaust |
| |
| Physical |
Dimensions
(H" x W" x D") |
100 kW: 62.5 x 48 x 31.5 in (158.8 x 121.9 x 80.0 cm)
150 kW: 62.5 x 48 x 31.5 in (158.8 x 121.9 x 80.0 cm)
200 kW: 62.5 x 96 x 31.5 in (158.8 x 243.8 x 80.0 cm)
300 kW: 62.5 x 96 x 31.5 in (158.8 x 243.8 x 80.0 cm)
400 kW: 62.5 x 192 x 31.5 in (158.8 x 487.7 x 80.0 cm)
450 kW: 62.5 x 144 x 31.5 in (158.8 x 365.8 x 80.0 cm)
600 kW: 62.5 x 192 x 31.5 in (158.8 x 487.7 x 80.0 cm) |
| Weight |
100 kW: 1600 lbs (725.8 kg)
150 kW: 2100 lbs (952.5 kg)
200 kW: 3200 lbs (1451.5 kg)
300 kW: 4200 lbs (1905.1 kg)
400 kW: 6400 lbs (2903.0 kg)
450 kW: 6300 lbs (2857.6 kg)
600 kW: 8400 lbs (3810.2 kg) |
| |
| Output |
| Ripple |
See Model Charts |
| Line Regulation |
Voltage Mode: ± 0.004% of full scale
Current Mode: ± 0.02% of full scale |
| Load Regulation |
Voltage Mode: ± 0.01% of full scale
Current Mode: ± 0.04% of full scale |
| Load Transient Response |
2 ms to recover within ±1% of regulated output with a 50% to 100% or 100% to 50% step load change |
| Efficiency |
≥ 86% |
| Stability |
± 0.10% for 8 hrs. after 30 min. warmup |
| Isolation |
Maximum input voltage to ground: ±2500 Vac
User inputs and outputs: referenced to Earth ground
For models less than or equal to 1000 Vdc:
Maximum output voltage to ground: ±1000 Vdc
For models greater than 1000 Vdc:
Maximum output voltage to ground: ±4000 Vdc |
| |
| Programming Levels and Accuracy of Full Scale |
|
Voltage
Set Point |
Current
Set Point |
OVT
Set Point |
OCT
Set Point |
| Remote Analog Programming Accuracy |
± 0.50% |
± 0.75% |
± 0.50% |
± 0.75% |
| Digital Programming Accuracy |
± 0.50% |
± 0.75% |
± 0.50% |
± 0.75% |
| Remote Analog Programming Levels |
0 - 10.0 Vdc |
0 - 10.0 Vdc |
0 - 11.0 Vdc |
0 - 11.0 Vdc |
| |
| Monitoring Levels and Accuracy of Full Scale |
|
Output Voltage |
Output Current |
| Remote Analog Monitoring Accuracy |
± 0.50% |
± 0.75% |
| Digital Monitoring Accuracy |
± 0.50% |
± 0.75% |
| Remote Analog Monitoring Levels |
0 - 10.0 V |
0 - 10.0 V |
| |
| Control Limits |
| Remote Sense Limits |
3% maximum voltage drop from output to load |
| Period Programming Limits |
Minimum period: 10 msec
Maximum Period: 9997 sec or 2.77 hours |
| Digital control inputs and outputs limits |
Input voltage: 0 to 10 Vdc
Output voltage: 0 to 10 Vdc, 5 mA drive capacity |
|